Place of Origin: | BEIJING,CHINA |
---|---|
Brand Name: | GFUVE |
Model Number: | GF312D1 |
Minimum Order Quantity: | 1SET |
Packaging Details: | CARTON |
Delivery Time: | 1-2WEEKS |
Payment Terms: | T/T, Western Union, MoneyGram |
Supply Ability: | 1500SETS/MONTH |
Resolution: | 6”TFT (640×480) | Accuracy: | 0.05%, 0.1% |
---|---|---|---|
Power Supply: | 220V±10%, 50/60Hz | Communication Port: | RS232 |
Test Voltage Range: | Phase To Netural 0-480V (Phase To Phase 0-830V) | Test Current Range: | 0-12A |
Harmonic: | 2nd-64st | Frequency: | 40-70Hz |
Dimension: | 245×162×60MM | Weight: | 1.8KG |
Ambient Temperature: | -10°C To 55°C | Warranty: | 5 Years |
High Light: | 64st Harmonic Energy Meter Testing Kit,Multi Channel Energy Meter Testing Kit,Energy Meter Testing Kit 70Hz |
FEATURES
TECHNICAL PARAMETERS
1.Electrical parameters | ||
---|---|---|
Accuracy class | 0.05%, 0.1% | |
Display | 6”TFT (640×480) | |
Power supply | 220V±10%, 50/60Hz Li-polymer battery (size (mm): 110x51x16, nominal output voltage: 7.2V, capacity: 5000mAh) Power line supply (U1, UN), 85V-265V 50/60Hz |
|
Communication port | RS232 | |
Test voltage | ||
Range | Phase to Netural 0-480V (Phase to Phase 0-830V) | |
Error | ±0.05% (30V-480V) ±0.1% (5V-30V) |
|
Voltage measurement temperature drift | < 8 x 10 E-6/K | |
Voltage measurement relative humidity drift | < 8 x 10 E-6/RH | |
Voltage measurement stability | < 50 x10 E-6 | |
Voltage measurement long term stability | < 80 x 10 E-6/Year | |
Harmonic | 2nd-64st | |
Test current | ||
Range (direct connection) | 0-12A | |
Error (direct connection) | ±0.05% (100mA-12A) ±0.1% (10mA-100mA) |
|
Range (clamp CT) | 10mA-120A | |
Clamp CT | ![]() Test range:1mA-120A Accuracy:0.1% Ratio:1000:1 Internal diameter:13mm External diameter:33mm Lead cable:2.5m |
|
Three phase color label | L1=Red,L2=Yellow,L3=Blue | |
Error (camp CT) | ±0.1% (100mA-120A) | |
Current measurement temperature drift | < 8 x 10 E-6/K @ 10mA-120A | |
Current measurement relative humidity drift | < 8 x 10 E-6/RH@ 10mA-120A | |
Current measurement stability | < 50 x10 E-6 | |
Current measurement long term stability | < 80 x 10 E-6/Year | |
Harmonic | 2nd-64st | |
Power & Energy measure error | ||
Active power (direct connection) | ±0.05% (0.1A-12A) ±0.1% (0.01A-0.1A) |
|
Reactive power (direct connection) | ±0.1% (0.1A-12A) | |
Energy measure error | ||
Active energy (direct connection) | ±0.05% (0.1A-12A) ±0.1% (0.01A-0.1A) |
|
Reactive energy (direct connection) | ±0.1% (0.1A-12A) | |
Power/energy measurement temperature drift | < 15 x 10 E-6/K | |
Power/energy measurement relative humidity drift | < 12 x 10 E-6/RH@ 10mA-120A | |
Power/energy measurement stability | < 100 x10 E-6 | |
Power/energy measurement long term stability | < 160 x 10 E-6/Year | |
Error display | 5 digits with minimum three decimal places XX.XXX% | |
Phase angle | ||
Range | 0°-360° | |
Resolution | 0.01o | |
Error | ±0.05° | |
Frequency | ||
Range | 40-70Hz | |
Resolution | 0.001Hz | |
Error | 0.002Hz | |
Pulse input | ||
Input channel | 2 | |
Input level | 5-24V | |
Input frequency | Max. 2MHz | |
Pulse output | ||
Energy constant | 180000imp/kWh, 1800imp/kWh, 180imp/kWh | |
Pulse ratio | 1:1 | |
Output level | 5V | |
Pulse frequency | Standard 400Hz-1KHz, customized max 10KHz | |
Scanning head | ||
![]() ![]() |
The sampler is equipped with a bracket which can clip/install on the tested electronic and electromechanical meters, and the sampler can insert to the ‘orifice/slot’ in the center of the bracket. There are 3 status LED indicator: [AUTO] – scan the turn-plate of the energy meter [MANU] –Manual input pulse [LED] – Receive the LED energy pulse |
|
Function | Sensitivity can be intelligently adjusted according to ambient light intensity to ensure accuracy measurement. | |
Function | ||
Vector diagram | Yes | |
Waveform | Yes | |
Energy accumulation | Yes | |
Communication with PC | Yes | |
Overload protection | Yes | |
2.Cable and Accessories | ||
Test Cable | Voltage test cable 1SET Cable Length:2m (R,Y,B,Black) Current test calbe 1SET Cable Length:2m (R,Y,B,Black) |
|
Plug | Pin type 1SET (4black,2Red,2Yellow,2Green) 'U' type 1SET (4black,2Red,2Yellow,2Green) 'Ω' type 1SET (4black,2Red,2Yellow,2Green) Crocodile type 1SET (1Black,1Red,1Yellow,1Green) |
|
Accessories Bag | Yes | |
3.Mechanical parameters | ||
Instrument dimensions (W×H×D) (mm) | 245×162×60 | |
Instrument Weight (kg) | 1.8 | |
Carry case dimensions (W×H×D) (mm) | 450×320×185 | |
Carry case (kg) | 10.6 | |
4.Environmental conditions | ||
Ambient temperature | -10°C to 55°C | |
Relative humidity | 15%-95% | |
Environmental protection level | IP51 | |
5.Standard | ||
lsolation protection | IEC 61010-1:2001 | |
Energy measurement | IEC 60736 | |
Reference standard | IEC 62052-11 IEC62053-21 IEC62053-22 & IEC62053-23 IEC61010-1:2001 |
|
6.Calibration and maintenance | ||
Warranty | 5 years | |
Calibration | Lifelong free calibration service | |
Recommended calibration interval | Every two years |