Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
an exclusive current transformer, split core current transformer, current clamp & voltage transformer manufacturer.
Place of Origin: | BEIJING, CHINA |
---|---|
Brand Name: | GFUVE |
Certification: | ISO9001, CE, UL, KEMA |
Model Number: | GF303 |
Minimum Order Quantity: | 1SET |
Packaging Details: | STANDARD EXPORT WOODEN BOX |
Delivery Time: | 2-3WEEKS |
Payment Terms: | L/C, D/P, D/A, T/T, Western Union, MoneyGram |
Supply Ability: | 200SETS |
NAME: | 3 Phase Voltage Current Electrical Power Calibrator | FUNCTION: | 2-63th Harmonics |
---|---|---|---|
CURRENT RANGE: | 0-20A | VOLTAGE RANGE: | 0-380V |
ACCURACY: | 0.05% | PHASE ANGLE: | 0-360.00 |
FREQUENCY: | 40-70HZ | USAGE: | Substation Test |
LCD: | 6.4 Inch Blue Light LCD | Weight: | 15KG |
Highlight: | three phase power source,3 phase power source |
GF303 portable 3 phase ac voltage and current standard Electrical Power Calibrator with 63th harmonics output
GF303 portable 3 phase ac voltage and current standard Electrical Power Calibrator with 63th harmonics output is suitable for power department, measuring department, quality control department, research units, and institutions of higher learning, and electric energy meter, power distribution terminals, power supply management, load control, power quality, reactive power compensation device and the production of enterprise etc.
Power calibrators and power quality calibrators GF333V2 - Three-phase Fully Automatic Test System with Reference Standard and Integrated Current and Voltage Source The Calmet GF303P portable test system consists of a three-phase reference meter of accuracy class 0.04% (or 0.1%) and an integrated three-phase current and voltage source up to 3x120A/600V
Split-phase power systems achieve their high conductor efficiency and low safety risk by splitting up the total voltage into lesser parts and powering multiple loads at those lesser voltages while drawing currents at levels typical of a full-voltage system. This technique, by the way, works just as well for DC power systems as it does for single-phase AC systems. Such systems are usually referred to as three-wire systems rather than split-phase because “phase” is a concept restricted to AC.
GF303 is electric AC/DC power and energy calibrator for calibration of power meters, power transducers, power quality analysers and generally all kinds of power measuring devices. AC voltage, current, power and energy functions have calibrated phase shift in frequency range from 45 Hz to 65Hz with resolution as good as 0.001 Hz.
As power grids get bigger and carry more power, the need for quick, reliable disconnection when faults occur becomes more urgent. The purpose of protective relay equipment is to sense fault states and trip circuit breakers. If a fault isn’t corrected early, personal injuries and damage can occur. Megger’s next generation of programmable secondary relay test systems are designed specifically to test microprocessor, solid state and electromechanical relays. New generation single phase and three phase test systems with remote control facilities and analytics software can make life much easier for protection test engineers.
FEATURES
PARAMETERS
Electrical parameters | |
---|---|
Accuracy class | 0.05%, 0.1% |
Power supply | Single phase AC 85V-265V, 50/60 Hz |
AC Voltage output | |
Range (U1, U2, U3 phase) | 57.7V/100V/220V/380V, switch automatically (max 420V) |
Adjustment resolution | 0.01%, 0.1%, 1%, 10%, |
Accuracy | 0.05% RG |
Stability | 0.005% RG/1min |
Distortion degree | better than 0.1% (not capacitive load) |
Load Capacity | 25VA |
Full load regulation rate | Less than 0.01% RG |
Full load regulation time | Less than 1mS |
Temperature drift | 8 PPM / °C |
Long-term stability | 60 PPM/year |
AC Current output | |
Range (I1, I2, I3 phase) | 0.1/0.25A/0.5A/1A/5A/10A/20A, switch automatically |
Adjustment resolution | 0.01%, 0.1%, 1%, 10%, |
Accuracy | 0.05% RG |
Stability | 0.005% RG/1min |
Distortion degree | better than 0.1% (not capacitive load) |
Load capacity | 25VA |
Full load regulation rate | Less than 0.01% RG |
Full load regulation time | Less than 1mS |
Temperature drift | 8 PPM/°C |
Long-term stability | 60 PPM/year |
Power output | |
Active power accuracy | 0.05% |
Reactive power accuracy | 0.1% |
Stability | 0.005% RG/1min |
Phase | |
Range | 0°-359.99° |
Adjustment resolution | 0.01°, 0.1°, 1°, 10° |
Accuracy | 0.03° |
Power factor | |
Adjusting range | -1 to 0 to +1 |
Resolution | 0.0001 |
Accuracy | 0.0005 |
Frequency | |
Range | 40-65Hz or 40-400Hz (option) |
Adjustment resolution | 0.001Hz, 0.01Hz, 0.1Hz, 1Hz |
Accuracy | 0.002Hz |
Temperature drift | 0.5PPM/°C |
Long-term stability | 4 PPM/year |
Harmonic | |
Harmonic times | 2-128 |
Adjustment resolution | 0.1% (compared with fundamental wave) |
Harmonic content (compared with fundamental wave) | |
Voltage | ≤40% |
Current | ≤40% |
Phase | 0°-360° |
Capacitive load capacity | |
0 - 280 V | 1uF |
280 - 420 V | 0.6uF |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | 450x380x160 |
Weight (kg) | 18 |
Environmental conditions | |
Working temperature | 0°C to 40°C |
Storage conditions | -30°C to 60°C |
Relative humidity | ≤85% |
SELECTION GUIDE
No. | Accuracy | Voltage range | Current range | Weight | Remark |
---|---|---|---|---|---|
3030601 | 0.10% | 0-264V | 0-6A | 12KG | |
3030605 | 0.05% | 0-264V | 0-6A | 12KG | |
3031201 | 0.10% | 0-420V | 0-12A | 13.5KG | |
3031205 | 0.05% | 0-420V | 0-12A | 13.5KG | |
3032001 | 0.10% | 0-420V | 0-20A | 18KG | |
3032005 | 0.05% | 0-420V | 0-20A | 18KG | |
303H0601 | 0.10% | 0-300V | 0-6A | 15KG | XP system |
303H0605 | 0.05% | 0-300V | 0-6A | 15KG | XP system |
303H1201 | 0.10% | 0-420V | 0-12A | 18KG | XP system |
303H1205 | 0.05% | 0-420V | 0-12A | 18KG | XP system |
303H2001 | 0.10% | 0-420V | 0-20A | 20KG | XP system |
303H2005 | 0.05% | 0-420V | 0-20A | 20KG | XP system |